Difference between revisions of "CalibFix Users"

From DIDEAS Wiki
Jump to: navigation, search
 
(9 intermediate revisions by 3 users not shown)
Line 1: Line 1:
 
'''Calibration Fixture'''
 
'''Calibration Fixture'''
  
PowerFoot Calibration Procedure
+
PF Calibration Procedure
  
 
# First time cycle encoder board
 
# First time cycle encoder board
 
# Zero mechanical
 
# Zero mechanical
##bearings touching ramp
+
## Bearings must be touching ramp
##
 
 
# Check Firmware Revision using PF_CMD
 
# Check Firmware Revision using PF_CMD
 
## Check State Controller (SC)
 
## Check State Controller (SC)
 +
### svn:\\PowerFoot\tags\StateControl-751
 
## Check Motor Controller (MC)
 
## Check Motor Controller (MC)
 +
### svn:\\PowerFoot\tags\MotorControl-753
 
# Zero backdrive motor via EPOS UI
 
# Zero backdrive motor via EPOS UI
 +
## Move the A-frame until the ankle K3 spring roller just engages the ramp
 
## Run EPOS program
 
## Run EPOS program
## Status -> Reset Node
+
## Click Status -> Reset Node
## Clear Errors
+
## Click Clear Errors
## Enable EPOS and check for green light
+
## Click Enable EPOS and check for green light
 +
## Exit the EPOS program
 
#Run TestJig
 
#Run TestJig
 
## TestJig: Zero Angle
 
## TestJig: Zero Angle
### Move to position 0
+
### Move to position 20000 (External Motor Box (upper left of screen)
### Zero
+
#### In the Position menu line, enter 0 in the target box
### Move to position 20000
+
#### Click Go to Target
 
### Move to position -20000
 
### Move to position -20000
 
### Move to position 0
 
### Move to position 0
### Zero
+
### Repeat steps 1-3 twice
### Repeat 20000, -20000, 0, ZERO several times
+
### Zero the External Ankle Deg. reading
 +
#### In the External Encoder Box (lower right), click Zero in the Angle Deg. box
 
## TestJig: Parallel Spring Test
 
## TestJig: Parallel Spring Test
### Turn off Data Query
+
### Clear the Data Query check boxes
 
### Set the following parameters (others leave at 0)
 
### Set the following parameters (others leave at 0)
#### Sampling Rate 100
+
#### Sampling Rate 10
#### Duration 3000
+
#### Duration 3600
 
#### Initial 64000
 
#### Initial 64000
 
#### Final -38000
 
#### Final -38000
Line 35: Line 39:
 
#### Decel 0.3
 
#### Decel 0.3
 
#### RPM 22
 
#### RPM 22
 +
#### Move to position 64000
 +
#### Click Go to Target
 
### Test should run for ~45 minutes
 
### Test should run for ~45 minutes
 
## TestJig: Series Spring Test
 
## TestJig: Series Spring Test
 +
### Go to Motor Position 0
 +
### Click Query (not the check box) in the External Motor box
 +
### Zero the Ankle Deg.
 +
### Set the following parameters (others leave at 0)
 +
#### Sampling Rate 100
 +
#### Duration 3000
 +
#### Initial 46000
 +
#### Final 0
 +
#### Passes 20
 +
#### Accel 1.5
 +
#### Decel 1.5
 +
#### RPM 45000
 +
#### Move to position 0
 +
#### Click Query
 +
#### Zero the Ankle Deg
 +
#### Move to position 46000
 +
#### Click Query
 +
#### Click Go to Target
 +
### Test should run for ~3 minutes

Latest revision as of 16:15, 11 January 2010

Calibration Fixture

PF Calibration Procedure

  1. First time cycle encoder board
  2. Zero mechanical
    1. Bearings must be touching ramp
  3. Check Firmware Revision using PF_CMD
    1. Check State Controller (SC)
      1. svn:\\PowerFoot\tags\StateControl-751
    2. Check Motor Controller (MC)
      1. svn:\\PowerFoot\tags\MotorControl-753
  4. Zero backdrive motor via EPOS UI
    1. Move the A-frame until the ankle K3 spring roller just engages the ramp
    2. Run EPOS program
    3. Click Status -> Reset Node
    4. Click Clear Errors
    5. Click Enable EPOS and check for green light
    6. Exit the EPOS program
  5. Run TestJig
    1. TestJig: Zero Angle
      1. Move to position 20000 (External Motor Box (upper left of screen)
        1. In the Position menu line, enter 0 in the target box
        2. Click Go to Target
      2. Move to position -20000
      3. Move to position 0
      4. Repeat steps 1-3 twice
      5. Zero the External Ankle Deg. reading
        1. In the External Encoder Box (lower right), click Zero in the Angle Deg. box
    2. TestJig: Parallel Spring Test
      1. Clear the Data Query check boxes
      2. Set the following parameters (others leave at 0)
        1. Sampling Rate 10
        2. Duration 3600
        3. Initial 64000
        4. Final -38000
        5. Passes 20
        6. Accel 0.6
        7. Decel 0.3
        8. RPM 22
        9. Move to position 64000
        10. Click Go to Target
      3. Test should run for ~45 minutes
    3. TestJig: Series Spring Test
      1. Go to Motor Position 0
      2. Click Query (not the check box) in the External Motor box
      3. Zero the Ankle Deg.
      4. Set the following parameters (others leave at 0)
        1. Sampling Rate 100
        2. Duration 3000
        3. Initial 46000
        4. Final 0
        5. Passes 20
        6. Accel 1.5
        7. Decel 1.5
        8. RPM 45000
        9. Move to position 0
        10. Click Query
        11. Zero the Ankle Deg
        12. Move to position 46000
        13. Click Query
        14. Click Go to Target
      5. Test should run for ~3 minutes